The MGate 5119 is an industrial Ethernet gateway with 2 Ethernet ports and 1 RS-232/422/485 serial port. To integrate Modbus, IEC 60870-5-101, and IEC 60870-5-104 devices with an IEC 61850 MMS network, use the MGate 5119 as a Modbus master/client, IEC 60870-5-101/104 master, and DNP3 serial/TCP master to collect and exchange data with IEC 61850 MMS systems.
The MGate 5119 as an IEC 61850 MMS server, typically, requires the import of a SCL file generated by a 3rd party tool. This can be time-consuming and increase costs. To overcome this pain point, MGate 5119 has a built-in SCL generator, which can easily generate SCL files through the web console and make them available almost immediately saving configuration time and cost.
MGate 5119 Series gateways support Modbus RTU/ASCII/TCP, IEC 60870-5-101, IEC 60870-5-104, and IEC 61850 MMS Protocol Traffic Monitor for easy troubleshooting, especially during the installation stage. It is worth mentioning that traffic logs can be viewed in the popular troubleshooting tool, Wireshark. With this feature, you can easily analyze traffic to determine the root cause of a problem.
Ethernet Interface | |
10/100BaseT(X) Ports (RJ45 connector) | 2 Auto MDI/MDI-X connection |
Magnetic Isolation Protection | 1.5 kV (built-in) |
Ethernet Software Features | |
Industrial Protocols | Modbus TCP Client (Master), IEC 60870-5-104 Client, IEC 61850 MMS Server, DNP3 TCP Master |
Configuration Options | Web Console (HTTP/HTTPS), Device Search Utility (DSU) |
Management | ARP, DHCP Client, DNS, HTTP, HTTPS, SMTP, SNMP Trap, SNMPv1/v2c/v3, TCP/IP, Telnet, SSH, UDP, NTP Client |
MIB | RFC1213, RFC1317 |
Time Management | NTP Client |
Security Functions | |
Authentication | Local database |
Encryption | HTTPS, AES-128, AES-256, SHA-256 |
Security Protocols | SNMPv3 SNMPv2c Trap HTTPS (TLS 1.3) |
Serial Interface | |
Console Port | RS-232 (TxD, RxD, GND), 8-pin RJ45 (115200, n, 8, 1) |
No. of Ports | 1 |
Connector | DB9 male |
Serial Standards | RS-232/422/485 |
Baudrate | 50 bps to 921.6 kbps |
Data Bits | 7, 8 |
Parity | Even, Mark, None, Odd, Space |
Stop Bits | 1, 2 |
Flow Control | RTS Toggle (RS-232 only), RTS/CTS |
RS-485 Data Direction Control | ADDC® (automatic data direction control) |
Pull High/Low Resistor for RS-485 | 1 kilo-ohm, 150 kilo-ohms |
Terminator for RS-485 | 120 ohms |
Isolation | 2 kV (built-in) |
Serial Signals | |
RS-232 | TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND |
RS-422 | Tx+, Tx-, Rx+, Rx-, GND |
RS-485-2w | Data+, Data-, GND |
RS-485-4w | Tx+, Tx-, Rx+, Rx-, GND |
Serial Software Features | |
Industrial Protocols | Modbus RTU/ASCII Master, IEC 60870-5-101 Master (Balanced/Unbalanced), DNP3 Serial Master |
Modbus RTU/ASCII | |
Mode | Master |
Functions Supported | 1, 2, 3, 4, 5, 6, 15, 16, 23 |
Max. No. of Commands | 128 |
Modbus TCP | |
Mode | Client (Master) |
Functions Supported | 1, 2, 3, 4, 5, 6, 15, 16, 23 |
Max. No. of Server Connections | 32 |
Max. No. of Commands | 128 |
IEC 60870-5-104 | |
Mode | Client |
Objects Supported | Single point Double point Step position Bit string of 32 bit Measured value (normalized) Measured value (scaled) Measured value (floating) Integrated totals |
Max. No. of Server Connections | 32 |
Max. No. of Information Objects | 1200 points |
IEC 60870-5-101 | |
Mode | Master (Balanced/Unbalanced) |
Objects Supported | Single point Double point Step position Bit string of 32 bit Measured value (normalized) Measured value (scaled) Measured value (floating) Integrated totals |
Max. No. of Slave Connections | 1 (Balanced), 31 (Unbalanced) |
Max. No. of Information Objects | 1200 points |
DNP3 Serial | |
Mode | Master |
Objects Supported | Binary inputs Analog inputs Counters Frozen counters Binary outputs Analog outputs |
Max. No. of Outstation Connections | 16 |
Max. No. of Objects | 1200 points |
DNP3 TCP | |
Mode | Master |
Objects Supported | Binary inputs Analog inputs Counters Frozen counters Binary outputs Analog outputs |
Max. No. of Outstation Connections | 16 |
Max. No. of Objects | 1200 points |
IEC 61850 | |
Mode | MMS Server |
Max. No. of Client Connections | 16 |
Max. No. of Datasets | 99 |
Max. No. of Reports | 99 |
Max. No. of Data Objects | 1200 points |
Memory | |
No. of Data Points Supported | 1,200 points |
microSD Slot | Up to 32 GB (SD 2.0 compatible) |
Power Parameters | |
Input Voltage | 12 to 48 VDC |
Input Current | 455 mA @ 12 VDC |
Power Connector | Screw-fastened Euroblock terminal |
Relays | |
Contact Current Rating | Resistive load: 2 A @ 30 VDC |
Physical Characteristics | |
Housing | Metal |
IP Rating | IP30 |
Dimensions | 36 x 120 x 150 mm (1.42 x 4.72 x 5.91 in) |
Weight | 517 g (1.14 lb) |
Environmental Limits | |
Operating Temperature | -40 to 75°C (-40 to 167°F) |
Storage Temperature (package included) | -40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
Standards and Certifications | |
Safety | EN 60950-1, IEC 60950-1, IEC 62368-1, UL 60950-1, EN 62368-1, UL 62368-1 |
EMC | EN 55032/35 |
EMI | CISPR 32, FCC Part 15B Class A |
EMS | IEC 61000-4-2 ESD: Contact: 8 kV; Air: 15 kV IEC 61000-4-3 RS: 80 MHz to 1 GHz: 20 V/m IEC 61000-4-4 EFT: Power: 4 kV; Signal: 4 kV IEC 61000-4-5 Surge: Power: 2 kV; Signal: 4 kV IEC 61000-4-6 CS: 10 V/m IEC 61000-4-8 PFMF: 100 A/m |
Freefall | IEC 60068-2-32 |
Shock | IEC 60068-2-27 IEC 61850-3 Edition 2.0 |
Power Substation | IEEE 1613, IEC 61850-3 |
Vibration | IEC 60068-2-6, IEC 60068-2-64, IEC 61850-3 Edition 2.0 |
MTBF | |
Time | 1,180,203 hrs |
Standards | Telcordia SR332 |
Warranty | |
Warranty Period | 5 years |
Details | See www.moxa.com/warranty |
Name | Type | Version | Release Date |
Notice: Undefined variable: detail_ap in /opt/lampp/htdocs/productview.php on line 639