Output Voltage
12V
Output Power
25W
Output Current
2.1A
Input Voltage Range
90-264Vac
Dimensions (L x W x D)
91 x 53 x 55.6 mm
3.58” x 2.09” x 2.19”
Unit Weight
0.14 kg (0.31 lb)
Output | |
Output Current | 2.1A |
Output Voltage | 12V |
Output Voltage Adjustment Range | 11.5-14.5Vdc |
Output Power | 25W |
Line Regulation | < 0.5% (@ 90-264Vac input, 100% load) |
Load Regulation | < 1% (@ 90-264Vac input, 0-100% load) |
PARD | < 100mVpp |
Start-up Time | < 2000ms @ nominal input (100% load) |
Hold-up Time | > 25ms @ 115Vac (100% load) > 60ms @ 230Vac (100% load) |
Dynamic Response (Overshoot & Undershoot O/P Voltage) | ± 5% @ 90-264Vac input, 10-100% load (Slew Rate: 0.1A/μS, 50% duty cycle @ 5Hz to 100Hz) |
Start-up with Capacitive Loads | 3,000μF Max |
Input | |
Input Voltage | 100-240Vac |
Input Voltage Range | 90-264Vac |
Nominal Input Frequency | 50-60Hz |
Input Frequency Range | 47-63Hz |
DC Input Voltage Range | 125-375Vdc |
Input Current | < 0.80A @ 115Vac, < 0.60A @ 230Vac |
Efficiency at 100% load | > 85.0% @ 115Vac & 230Vac |
Max Inrush Current | < 25A @ 115Vac, < 50A @ 230Vac |
Leakage Current | < 0.25mA @ 240Vac |
Mechanical | |
Case Chassis / Cover | Plastic |
Indicator | Green LED (DC OK) |
Cooling System | Convection |
Input Terminal | 2 Pins (Rated 300V/25A) |
Output Terminal | 4 Pins (Rated 300V/25A) |
Noise Sound Pressure Level (SPL) | < 25dBA |
Wire | Input / Output : AWG 24-12 |
Unit Weight | 0.14 kg (0.31 lb) |
Dimensions | 91 x 53 x 55.6 mm 3.58” x 2.09” x 2.19” |
Environment | |
Vibration (Operating) | IEC 60068-2-6, Sine Wave: 10-500Hz @ 19.6m/S² (2G peak); 10 min per cycle, 60 min for all X, Y, Z directions |
Shock (Operating) | IEC 60068-2-27, Half Sine Wave: 4G for a duration of 22ms, 3 shocks for each 3 directions, 9 times in total |
Operating Temperature | -25°C to +71°C |
Storage Temperature | -25°C to +85°C |
Power De-rating | > 55°C de-rate power by 2.5% / °C |
Operating Humidity | 5 to 95% RH (Non-Condensing) |
Pollution Degree | 2 |
Over Voltage Category | II |
Protections | |
Overvoltage | < 17.4V, SELV Output, Latch Mode |
Overload / Overcurrent | > 130% of rated load current, Hiccup Mode, Non-Latching (Auto-Recovery) |
Over Temperature | < 75°C Surrounding Air Temperature @ 100% load, Latch Mode |
Short Circuit | Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed) |
Degree of Protection | IP20 |
Protection Against Shock | Class II (No Primary Earth connection is required) |
Reliability | |
MTBF | > 500,000 hrs. as per Telcordia SR-332 I/P: 100Vac, O/P: 100% load, Ta: 35°C |
Expected Cap Life Time | 10 years (115Vac & 230Vac, 50% load @ 40°C) |
Safety | |
Electrical Safety | TUV Bauart EN 60950-1 UL/cUL recognized UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E131881) CB scheme IEC 60950-1, Limited Power Source (LPS) |
CE | In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU |
Galvanic Isolation | Input to Output 3.0KVac |
Industrial Control Equipment | UL/cUL listed UL 508 and CSA C22.2 No. 107.1-01 (File No. E338991) |
Material and Parts | RoHS Directive 2011/65/EU Compliant |
EMC | |
Emission | CISPR 32, EN 55032, FCC Title 47: Class B |
Immunity | EN 55024 |
Name | Type | Version | Release Date | |
DRC-12V30W1AZ Datasheet | Datasheet | V1.0 | 22 April 2020 |