Output Voltage
24V
Output Power
31W
Output Current
1.3A
Input Voltage Range
85-264Vac
Dimensions (L x W x H)
105 x 50 x 25.6 mm (Open Frame)
125 x 60 x 36 mm (Enclosed)
4.13" x 1.96" x 1.00” (Open Frame)
4.92" x 2.36" x 1.41" (Enclosed)
Unit Weight
0.11 kg (Open Frame)<br>0.20 kg (Enclosed) (0.24 lb)
Output Current 1.3A |
Output Voltage 24V |
Output Voltage Adjustment Range 21.6-26.4Vdc |
Output Power 31W |
Line Regulation < 96mV |
Load Regulation < 150mV |
Start-up Time 500ms typ. @ 100Vac |
Hold-up Time 20ms Typ. @ 100Vac |
Dynamic Response (Overshoot & Undershoot O/P Voltage) ± 5% @ 0-50% load and 50-100% load |
Start-up with Capacitive Loads 8,000µF Max |
Residual Ripple/PARD (20MHz) < 120mVpp @ 0°C to 50°C, |
Ripple & Noise < 150mVpp @ 0°C to 50°C, |
Input Voltage 100-240Vac |
Input Voltage Range 85-264Vac |
Nominal Input Frequency 50-60Hz |
Input Frequency Range 47-63Hz |
Input Current 0.65Atyp. @100Vac, |
Efficiency at 100% load 85.0% typ. @ 100Vac, |
Max Inrush Current 15A typ. @ 100Vac, |
Leakage Current 0.1mA @ 100Vac, |
Case Chassis / Cover SGCC | |
Cooling System Convection | |
Input/Output Terminal JST B3P5-VH (LF)(SN) | |
Signal JST B4P-VH (LF)(SN) | |
Wire AWG 22-18 | |
Unit Weight 0.11 kg (Open Frame)<br>0.20 kg (Enclosed) (0.24 lb) | Dimensions 105 x 50 x 25.6 mm (Open Frame) |
Operating Temperature
-10°C to +70°C
Storage Temperature
-25°C to +75°C
Power De-rating
>50°C de-rate power by 2.5% /°C, <90Vac de-rate power by 2%/V
Operating Humidity
5 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)
IEC60068-2-27,196.1m/S² (20G), 11ms, once along X, Y, and Z axis
Vibration (Non-Operating)
IEC60068-2-6, 10Hz to 55Hz@19.6m/S² (2G); 3min period, 60 min per axis for all X, Y, Z direction
Overvoltage 27.6-33.6V, Latch Mode |
Overload / Overcurrent > 105% of rated load current, Hicc-up Mode, Non-Latching (Auto-Recovery) |
Over Temperature Latch Mode |
Short Circuit Hicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed) |
Protection Against Shock Class I with Primary Earth connection |
MTBF > 200,000 hrs. as per JEITA RCR-9102B |
Expected Cap Life Time 10 years (115Vac, 50% load @ 40°C) |
Electrical Safety
TUV Bauart: EN 60950-1, EN 62368-1
UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E131881), UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E131881)
CB scheme : IEC 60950-1, IEC 62368-1
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
Galvanic Isolation
Input to Output: 3.0 KVac
Input to Ground: 2.0 KVac
Output to Ground: 0.5 KVac
Emission CISPR 32, EN 55032, FCC Title 47: Class B |
Harmonic Current Emissions IEC/EN 61000-3-2, Class A |
Voltage Fluctuation and Flicker IEC/EN 61000-3-3 |